Energy System



The Datacenter has two medium voltage separate entrances 13.2 KV fed from two different substations of Edesur provider.

Additionally, it has a self-generation plant of electricity with a capacity of 4 MVA which consists  of  2  sets of Caterpillar power generators, of 2 MVA each, offering the possibility of extending it  up to  6 MVA. Both sets are preheated 24 hours to obtain the lowest response time in the boot.

Each generator is equipped with a fuel tank of 2.000 liters which is used for testing operation. Additionally there are two main tanks which  are   interconnected and  can  store  up  to   70,000  liters   of  fuel which allows continuous  operation of 7 days without fill the main tanks.

The uninterruptible power supply system  has an UPS configuration in N + 1 mode with capacity of 1.8 MVA,  configured   as   a   redundant  system  that   ensures mechanisms for constant regulated energy flow.

 

Service power supply (220VAC / 380VAC)

• Double plant dry transformers (2 + 3 MVA MVA).

• Back up of 1 hour of battery to support the UPS system.

• The supply of energy to customers is through PDUs (PowerDelivery Unit) located in each Datacenter room which deliver energy in a redundant scheme from  the UPSs.